The Ontario Fire Code requires a daily check of the fire alarm control panel, monthly checks of extinguishers and battery emergency lights, and an annual round of inspections and tests. Keep the records at the building for at least two years.
An Ontario fire inspector checks three things: that each fire protection system in your building is maintained on the schedule the Fire Code sets, that exits and storage areas are safe, and that you can show the records. This checklist goes system by system, with what the inspector looks at, who does the work, and how often. Use it to prepare for an inspection or to set up a year of maintenance for a commercial building.
Under section 19 of the Fire Protection and Prevention Act, a fire inspector can enter commercial premises at reasonable times without a warrant to inspect them. Inspectors can examine documents, run tests, take photographs, and ask questions. When they find a problem, section 21 lets them order the owner or occupant to fix it. A building that keeps its systems and records current turns that visit into a short walk-through.
What does a fire inspector check in Ontario?
Inspectors look at every system the Fire Code requires your building to maintain, plus the conditions that start or spread fires. Mississauga Fire and Emergency Services publishes the violations its inspectors find most often:
- Blocked exits
- Faulty or missing fire protection systems, including expired extinguishers
- Flammable materials stored improperly
- Overcrowding
- Electrical hazards
- Failure to do required maintenance
Most of that list comes down to two habits: keeping systems on schedule and keeping exits and storage areas clear. The sections below cover each system in the order an inspector tends to meet them.
Portable fire extinguishers
Extinguishers are the quickest system for an inspector to check, because the tag shows at a glance whether the annual maintenance happened.
What the inspector looks at:
- A tag on each extinguisher showing the maintenance date, the servicing company, and the signature of the person who did the work
- Extinguishers that are easy to see and accessible at all times, not hidden behind stock or furniture
- Mounting height: the top of the extinguisher no more than 1.5 m above the floor for a unit of 18 kg or less, and 1.1 m for a heavier unit without wheels
- Extinguishers located in or next to the corridors and aisles that lead to exits
- The right class of extinguisher for each hazard, including Class K units for cooking operations
- A permanent record for each unit showing the maintenance date, the examiner's name, and any work carried out
Who does the work and how often: Your staff inspect each extinguisher every month. A qualified technician maintains them to NFPA 10, which includes the annual inspection and new tag.
Our guides cover each piece in more depth: what an annual inspection costs, which type of extinguisher each area needs, how many extinguishers a building needs and where they go, and what fire extinguisher certification means.
Emergency lighting and exit signs
Emergency lights and exit signs can fail without anyone noticing, because they sit idle until the power goes out. The monthly tests in the Fire Code catch those failures.
What the inspector looks at:
- Exit signs that are clearly visible, clean, and legible
- Exit signs and exit lighting lit whenever the building is occupied
- Battery units (self-contained emergency lighting) with working pilot lights, clean terminals, and clean batteries
- Records of the monthly test and the annual full-duration test
Who does the work and how often:
- Every month: inspect battery emergency lighting units and test that the lights come on when the normal power fails. Exit signs with a battery backup get the same monthly check.
- Every 12 months: run a full-duration test on battery units under simulated power failure, then check the charging system against the manufacturer's specifications. Other emergency lights and exit signs are inspected at least every 12 months.
Our post on emergency lighting inspection in Ontario walks through the monthly and annual tests. For green running man signs, red EXIT signs, and signs that fail their test, see exit sign requirements in Ontario.
Fire alarm system
The fire alarm system comes with its own set of records, and inspectors ask to see them.
What the inspector looks at:
- An annual inspection and test of the whole system to CAN/ULC-S536
- A record for each device, component, and circuit showing whether it works
- A current description of the system, kept in the building at an approved location
- For monitored systems, a record of whether the test signals reached the monitoring station
- A clear panel, with no trouble signals left unattended
Who does the work and how often:
- Every day: someone on your staff checks the central alarm and control facility for any trouble indication.
- Every 12 months: a technician performs the annual inspection and test. The Fire Code requires that person to have completed a program or course acceptable to the Fire Marshal and to show you the certificate if you ask. The owner is responsible for checking.
If any part of the fire alarm system is shut down, the Fire Code requires you to notify the fire department, the building occupants, and your supervisory staff. Our guide to the annual fire alarm inspection in Ontario covers the visit itself, tenant notices, and the report.
Sprinkler systems
Sprinkler inspection follows NFPA 25, with weekly, monthly, quarterly, annual, and five-year tasks. Our post on commercial sprinkler system inspection in Ontario lays out the full schedule.
What the inspector looks at under the Fire Code itself:
- Notice to the Chief Fire Official before any alterations, additions, or repairs that interrupt the sprinkler system
- No sprinkler control valve or water supply shut down for more than 24 hours without notifying the Chief Fire Official
- When the system or any part of it is shut down, notice to the fire department, the building occupants, and the supervisory staff
- Inspection records for the NFPA 25 schedule
Kitchen suppression systems
Restaurants and commercial kitchens add two items to the checklist: the hood suppression system and the extinguishers that protect the cooking line. The Fire Code requires portable extinguishers suitable for Class K fires to protect cooking operations. Our post on kitchen fire suppression system inspection in Ontario explains the inspection schedule for the hood system and how it differs from hood cleaning.
Fire safety plan and posted procedures
Many commercial buildings need an approved fire safety plan. The Fire Code requires one for any building with an assembly occupancy, for offices and stores with more than 300 occupants, for industrial buildings above set occupant loads, and for any building of four storeys or more, counting storeys below grade.
What the inspector looks at:
- A plan that has been prepared, approved, and put into practice
- The plan kept in the building at an approved location
- A review at least every 12 months, with revisions when the use of the building changes
- At least one copy of the fire emergency procedures posted on each floor area
- A fire drill for supervisory staff at least once every 12 months
Our guide to fire safety plans in Ontario covers who needs a plan, what goes in it, and what to post on each floor.
Exits, storage, and housekeeping
Housekeeping problems fill much of Mississauga's common-violations list, and staff can fix most of them on the day.
Walk the building and check:
- Exit doors, corridors, and stairwells are clear of storage, furniture, and deliveries
- Flammable liquids and gas cylinders sit in their designated storage areas, away from exits and heat sources
- Storage rooms, electrical rooms, and mechanical rooms are free of combustible clutter
- Extension cords and power bars aren't serving as permanent wiring
- Occupant numbers in assembly spaces stay within the posted limits
None of these items needs a contractor. A monthly walk-through by a property or facility manager catches them before an inspector does.
Records the inspector will ask for
If you can't produce a record, you can't show the inspector the work was done. The Fire Code requires records to stay at the building for at least two years, and you must keep at least the most recent record of each test or inspection and the one before it. Initial verification or test reports for fire protection systems installed after November 21, 2007 stay on file for the life of the system.
Keep these together in one binder or one shared folder:
- Extinguisher service records and the latest inspection report
- Monthly and annual emergency lighting and exit sign test records
- The annual fire alarm inspection report, device records, and the system description
- Sprinkler inspection and test reports
- Kitchen suppression service reports, if you have a commercial kitchen
- The approved fire safety plan and the date of its last review
- Fire drill records
How to prepare in the week before an inspection
If you know an inspection is coming, a few hours of preparation spread over the week keeps the visit short. Work through this list with whoever will walk the building with the inspector.
- Pull the records binder together and check that each system's latest report is in it, with the dates inside the required intervals.
- Walk every floor and read the date on each extinguisher tag. Book the annual service now for any unit coming due.
- Check the fire alarm panel for trouble signals and ask your fire alarm contractor about any you can't clear.
- Press the test button on a sample of emergency lights and battery-backed exit signs, and book a repair for any sign or light that stays dark.
- Clear storage from exits, corridors, stairwells, and electrical and mechanical rooms.
- Confirm the fire safety plan is in its approved location and that its last review falls within the past 12 months.
- Have keys ready for every locked room, including electrical rooms, sprinkler rooms, and the roof.
Pick one person to accompany the inspector, someone who knows the building and where the records live. When the inspector points out a problem, write it down on the spot so nothing gets missed if an order follows.
A fire safety calendar for property managers
The Code sets the intervals. Putting them on one calendar keeps a building from drifting out of compliance between inspections.
Every day
- Check the fire alarm control panel for trouble signals.
Every month
- Inspect each portable extinguisher.
- Inspect and test battery emergency lighting units and battery-backed exit signs.
- Complete the monthly sprinkler tasks in your NFPA 25 schedule.
- Walk the exits, storage rooms, and electrical rooms.
Every 12 months
- Annual extinguisher maintenance and new tags.
- Full-duration test of battery emergency lighting, and inspection of other emergency lights and exit signs.
- Annual fire alarm inspection and test to CAN/ULC-S536.
- Annual sprinkler and kitchen suppression inspections.
- Fire safety plan review and a fire drill for supervisory staff.
Booking the annual work in the same month means fewer visits to arrange and fewer days of disruption. With Boss Fire, extinguishers and emergency lighting done in the same visit share one service call fee.
Running the same checklist across several sites
Property managers with several buildings face a second problem: each site drifts onto its own schedule, and tags expire in different months. A single calendar across the whole portfolio fixes that. One company services every site to the same standard, and you get one set of reports to review. Our national accounts program is built for multi-site businesses and property portfolios.
What happens if the inspector finds a problem
If an inspector finds a contravention, section 21 of the Fire Protection and Prevention Act lets them order the owner or occupant to fix it. Orders can cover repairs, fire alarms and detection, fire suppression, means of egress, the fire safety plan, and any other breach of the Fire Code. Contravening the Fire Code is an offence under the Act. On conviction, fines reach $50,000 for an individual's first offence and $500,000 for a corporation's first offence. Our guide to clearing a fire inspection order covers what to do next, step by step.
Get your building inspection-ready with Boss Fire
Boss Fire inspects and maintains fire extinguishers, emergency lighting and exit signs, fire alarms, sprinklers, and kitchen suppression systems for commercial and industrial buildings across the GTA and the surrounding region, from Niagara to Oshawa and north to Barrie. Our technicians are NFPA-certified, our fire alarm technicians are registered with the CFAA, and Boss Fire carries $5 million in liability insurance.
Start with the free two-minute compliance check, then send us your building details. We answer with an itemized quote the same business day, and in the GTA we can be on site within 48 hours.
Sources and references
- Fire Protection and Prevention Act, 1997, sections 19 (inspection), 21 (inspection orders), and 28 (offences and fines)
- Ontario Fire Code, O. Reg. 213/07, Division B, Article 1.1.2.2 (records)
- Ontario Fire Code, O. Reg. 213/07, Division B, Articles 2.7.3.1 to 2.7.3.3 (exit signs and emergency lighting), 2.8.1.1, 2.8.2.1, 2.8.2.8, and 2.8.3.2 (fire safety planning and drills)
- Ontario Fire Code, O. Reg. 213/07, Division B, Articles 6.2.1.3 and 6.2.1.4 (extinguisher location), 6.2.4.2 and 6.2.4.3 (mounting height), 6.2.6.12 (Class K), 6.2.7.1 to 6.2.7.5 (inspection, tags, and records)
- Ontario Fire Code, O. Reg. 213/07, Division B, Articles 6.3.1.3, 6.3.2.2, and 6.3.2.3 (fire alarm systems), 6.5.2.1, 6.5.2.2, and 6.5.2.4 (sprinkler shutdowns), and 6.7.1.6 to 6.7.1.8 (emergency lighting and exit signs)
- Ontario Fire Code, O. Reg. 213/07, Division C, Articles 1.2.1.1 and 1.2.1.2 (fire alarm technician qualifications)
- City of Mississauga, Fire and Emergency Services, common Fire Code violations
Frequently Asked Questions
What does a fire inspection check for? +
A fire inspector checks that each fire protection system in the building is maintained on the Fire Code schedule, that exits are clear, and that the owner can show the records. That covers extinguisher tags, emergency lights and exit signs, the fire alarm system, sprinklers, kitchen suppression, the fire safety plan, and housekeeping such as storage and electrical hazards.
Are fire inspections mandatory in Ontario? +
The Ontario Fire Code requires building owners to inspect and test fire protection systems on set schedules, such as a monthly inspection of each extinguisher and an annual inspection and test of the fire alarm system. Separately, the Fire Protection and Prevention Act gives fire inspectors the power to enter and inspect premises and to order the owner to fix what they find.
What are the fire inspection requirements in Ontario? +
Most requirements come from Division B of the Ontario Fire Code. Extinguishers are inspected monthly and maintained to NFPA 10, battery emergency lights are inspected and tested monthly with a full-duration test every 12 months, fire alarm systems are inspected and tested to CAN/ULC-S536, and buildings that need a fire safety plan must review it at least every 12 months.
How long do I need to keep fire inspection records in Ontario? +
The Fire Code requires records to stay at the building for at least two years, and you must keep at least the two most recent records of each test or inspection. Initial verification or test reports for fire protection systems installed after November 21, 2007 are kept for the life of the system.
Who is responsible for fire inspections in a leased building? +
A fire inspector can direct an order to the owner or the occupant, so both have a stake in the result. Your lease decides who arranges and pays for each system, so check it and agree on who books the work before a deadline arrives.